Calculator

kW to BTU/hr Conversion

❄️ kW to BTU/hr Converter

Professional Kilowatts to BTU per Hour Calculator | HVAC Design Tool

kW
Enter power in kilowatts (SI metric unit)
BTU/hr
Converted thermal power in BTU per hour
BTU/hr
Enter thermal power in BTU per hour
kW
Converted power in kilowatts
kW
Enter kilowatt values separated by commas

📐 Conversion Formula:

❄️ Common HVAC Equipment Ratings

1 kW = 3,412 BTU/hr
3.5 kW = 11,943 BTU/hr
5 kW = 17,061 BTU/hr
7 kW = 23,885 BTU/hr
10 kW = 34,121 BTU/hr
15 kW = 51,182 BTU/hr
20 kW = 68,243 BTU/hr
30 kW = 102,364 BTU/hr

📚 Complete Guide to kW and BTU/hr Conversion

Understanding Kilowatts and BTU per Hour

Kilowatts (kW) are the SI (International System of Units) standard measurement of power where 1 kilowatt equals 1,000 watts, universally used in electrical engineering, modern HVAC specifications (especially in Europe, Asia, and increasingly in commercial applications worldwide), and energy efficiency calculations. BTU per hour (BTU/hr or BTUH) measures thermal power—the rate of heat energy transfer over time—where BTU (British Thermal Unit) is defined as the amount of heat required to raise the temperature of one pound of water by one degree Fahrenheit at sea level. The unit BTU/hr expresses how many BTUs of thermal energy are transferred, produced, or removed per hour, making it the standard measurement in the US HVAC industry for air conditioning cooling capacity, furnace heating output, heat pump ratings, boiler capacity, and building thermal load calculations. The fundamental relationship: 1 kilowatt = 3,412.14 BTU per hour exactly, derived from the precise conversion: 1 watt = 3.412142 BTU/hr, therefore 1,000 watts (1 kW) = 3,412.142 BTU/hr. Understanding this conversion enables HVAC professionals to translate between metric electrical power specifications (kW) used in equipment documentation and imperial thermal capacity ratings (BTU/hr) familiar to US contractors and homeowners, facilitates comparison of international equipment specifications where European manufacturers rate chillers and heat pumps in kW while US manufacturers use BTU/hr or tons (12,000 BTU/hr per ton), supports electrical load calculations where BTU/hr-rated HVAC equipment must be converted to kW for circuit sizing and panel load determination, and enables energy efficiency analysis where metrics like SEER (Seasonal Energy Efficiency Ratio), EER (Energy Efficiency Ratio), and COP (Coefficient of Performance) require understanding both thermal output (BTU/hr) and electrical input (watts or kW) for accurate calculation of system efficiency.

Conversion Formulas

Kilowatts to BTU per Hour: \( \text{BTU/hr} = \text{kW} \times 3{,}412.14 \). Multiply kilowatts by 3,412.14 to convert to BTU per hour. Examples demonstrating common HVAC applications: 1 kW × 3,412.14 = 3,412.14 BTU/hr (small space heater); 2 kW × 3,412.14 = 6,824.28 BTU/hr (medium portable heater); 3.5 kW × 3,412.14 = 11,942.49 BTU/hr (typically rounded to 12,000 BTU/hr for standard 1-ton window air conditioner suitable for 400-550 sq ft); 5 kW × 3,412.14 = 17,060.7 BTU/hr (1.5-ton mini-split system); 7 kW × 3,412.14 = 23,884.98 BTU/hr (2-ton packaged unit); 10 kW × 3,412.14 = 34,121.4 BTU/hr (3-ton central air conditioning); 15 kW × 3,412.14 = 51,182.1 BTU/hr (4-ton residential or small commercial system); 20 kW × 3,412.14 = 68,242.8 BTU/hr (5-ton system); 30 kW × 3,412.14 = 102,364.2 BTU/hr (8.5-ton light commercial chiller). BTU per Hour to Kilowatts: \( \text{kW} = \frac{\text{BTU/hr}}{3{,}412.14} \) or \( \text{kW} = \text{BTU/hr} \times 0.000293071 \). Divide BTU/hr by 3,412.14 (or multiply by 0.000293071) to convert to kilowatts. Examples for common AC capacities: 6,000 BTU/hr ÷ 3,412.14 = 1.76 kW (small window unit, 150-250 sq ft); 9,000 BTU/hr ÷ 3,412.14 = 2.64 kW (medium window unit, 300-400 sq ft); 12,000 BTU/hr ÷ 3,412.14 = 3.52 kW (1-ton unit, 400-550 sq ft); 18,000 BTU/hr ÷ 3,412.14 = 5.28 kW (1.5-ton unit, 600-900 sq ft); 24,000 BTU/hr ÷ 3,412.14 = 7.03 kW (2-ton unit, 1,000-1,400 sq ft); 36,000 BTU/hr ÷ 3,412.14 = 10.55 kW (3-ton unit, 1,500-2,100 sq ft); 48,000 BTU/hr ÷ 3,412.14 = 14.07 kW (4-ton unit, 2,000-2,800 sq ft); 60,000 BTU/hr ÷ 3,412.14 = 17.58 kW (5-ton unit, 2,500-3,500 sq ft). These conversions are essential for HVAC system design, equipment selection across international manufacturers, electrical load calculations for proper circuit breaker sizing, energy efficiency evaluations, building code compliance, and thermal load analysis where engineers must translate between measurement systems depending on project specifications and equipment availability.

Comprehensive HVAC Power Conversion Table

Kilowatts (kW)BTU/hrTons of CoolingTypical Application
1 kW3,412 BTU/hr0.28 tonsPortable heater, small space heater
1.5 kW5,118 BTU/hr0.43 tonsSmall window AC (150-250 sq ft)
2 kW6,824 BTU/hr0.57 tonsWindow AC, dehumidifier
3.5 kW11,943 BTU/hr1.0 ton1-ton window/wall AC (400-550 sq ft)
5 kW17,061 BTU/hr1.4 tons1.5-ton mini-split (600-900 sq ft)
7 kW23,885 BTU/hr2.0 tons2-ton heat pump (1,000-1,400 sq ft)
10 kW34,121 BTU/hr2.8 tons3-ton central AC (1,500-2,100 sq ft)
12 kW40,946 BTU/hr3.4 tons3.5-ton residential system
15 kW51,182 BTU/hr4.3 tons4-ton home system (2,000-2,800 sq ft)
18 kW61,418 BTU/hr5.1 tons5-ton system (2,500-3,500 sq ft)
20 kW68,243 BTU/hr5.7 tonsLarge residential / small commercial
30 kW102,364 BTU/hr8.5 tonsLight commercial chiller
50 kW170,607 BTU/hr14.2 tonsCommercial HVAC system
100 kW341,214 BTU/hr28.4 tonsLarge commercial chiller

Air Conditioner Sizing and Selection

Converting between kW and BTU/hr enables proper air conditioner selection based on cooling requirements. Room Size Guidelines: General rule: 20 BTU/hr per square foot for standard 8-foot ceilings, moderate insulation, typical sun exposure. Small room (150-250 sq ft): Requires 3,000-5,000 BTU/hr (0.88-1.47 kW). Example: Bedroom 10×20 ft = 200 sq ft × 20 = 4,000 BTU/hr minimum (1.17 kW). Select 5,000-6,000 BTU/hr (1.5-1.8 kW) unit. Medium room (250-400 sq ft): Requires 5,000-8,000 BTU/hr (1.47-2.34 kW). Example: Bedroom 15×25 ft = 375 sq ft × 20 = 7,500 BTU/hr (2.2 kW). Select 8,000 BTU/hr (2.34 kW) unit. Large room (400-550 sq ft): Requires 8,000-12,000 BTU/hr (2.34-3.52 kW). Example: Master bedroom 20×25 ft = 500 sq ft × 20 = 10,000 BTU/hr (2.93 kW). Select 12,000 BTU/hr (3.52 kW) 1-ton unit. Whole-House Central AC: 1,000-1,400 sq ft home: 2-2.5 tons (24,000-30,000 BTU/hr or 7.03-8.79 kW); 1,500-2,000 sq ft home: 2.5-3.5 tons (30,000-42,000 BTU/hr or 8.79-12.31 kW); 2,000-2,500 sq ft home: 3.5-4 tons (42,000-48,000 BTU/hr or 12.31-14.07 kW); 2,500-3,000 sq ft home: 4-5 tons (48,000-60,000 BTU/hr or 14.07-17.58 kW). Adjustment Factors: Add 10% for above-average sun exposure or south/west-facing windows; add 4,000 BTU/hr (1.17 kW) for kitchen; add 600 BTU/hr (0.18 kW) per occupant beyond two people; subtract 10% for heavily shaded spaces; add 20-30% for high ceilings (10+ feet); add 15-25% for poor insulation; add 10% for top-floor apartments (heat from roof). Electrical Considerations: Cooling capacity (BTU/hr) ≠ electrical consumption (kW). AC efficiency measured by EER (Energy Efficiency Ratio) or SEER (Seasonal EER). EER = BTU/hr output ÷ watts input. Example: 12,000 BTU/hr (3.52 kW cooling) unit with EER 10 draws 1,200 watts (1.2 kW) electrical power. Converting cooling capacity (BTU/hr or kW cooling) to electrical draw requires dividing by EER or SEER. Modern units: EER 8-13; SEER 13-25. Higher numbers = better efficiency = lower electrical consumption for same cooling output. Understanding kW-BTU/hr conversion enables accurate AC sizing preventing undersized units (inadequate cooling, constant running, high humidity) and oversized units (short cycling, poor dehumidification, higher upfront cost, inefficient operation).

Heat Pump Specifications

Heat pumps provide both heating and cooling with capacities rated in BTU/hr or kW for each mode. Dual Rating System: Cooling capacity typically matches AC ratings (BTU/hr or tons); heating capacity usually 10-30% higher at moderate temperatures. Example: 3-ton (36,000 BTU/hr or 10.55 kW cooling) heat pump produces 40,000-45,000 BTU/hr (11.72-13.19 kW) heating at 47°F outdoor temperature. Temperature-Dependent Performance: Heat pump capacity decreases as outdoor temperature drops. At 47°F: 100% rated capacity; at 35°F: 85-90% capacity; at 17°F: 65-75% capacity; at 0°F: 40-50% capacity. Example: 4-ton unit rated 48,000 BTU/hr (14.07 kW) at 47°F produces only 31,200 BTU/hr (9.14 kW) at 0°F, requiring supplemental heat. Balance Point: Outdoor temperature where heat pump capacity equals building heat loss—below this temperature, auxiliary heat (resistance coils or furnace backup) engages. Well-insulated home: balance point 20-30°F; poorly insulated: 35-45°F. COP (Coefficient of Performance): COP = thermal output (kW) ÷ electrical input (kW). Modern heat pumps: COP 2.5-4.5 (250-450% efficient). Example: Heat pump drawing 3 kW electrical with COP 3.5 produces 10.5 kW (35,843 BTU/hr) heating. Converting: 10.5 kW × 3,412.14 = 35,827 BTU/hr heating output. HSPF (Heating Seasonal Performance Factor): Seasonal heating efficiency = total BTU/hr heating ÷ total watt-hours electrical input over heating season. HSPF 8-13 for modern units. Higher HSPF = better efficiency. Electrical Load Calculation: Sizing electrical service for heat pump requires converting heating/cooling capacity (BTU/hr) to electrical draw (kW). Example: 5-ton (60,000 BTU/hr or 17.58 kW cooling capacity) heat pump with SEER 16 draws approximately 3,750 watts (3.75 kW) cooling; with HSPF 10 draws 6,000 watts (6 kW) heating; auxiliary resistance heat 10-15 kW additional. Total electrical load: 16-21 kW, requiring 80-100 amp circuit. Converting between BTU/hr and kW enables proper heat pump selection matching building thermal load, circuit sizing for electrical installation, and efficiency calculations comparing different models.

Furnace and Boiler Capacity

Heating equipment capacity rated in BTU/hr (US) or kW (international) must match building heat loss. Residential Furnaces: Input capacity (fuel consumed) vs output capacity (useful heat delivered). Example: 100,000 BTU/hr (29.31 kW) input gas furnace at 95% AFUE (Annual Fuel Utilization Efficiency) produces 95,000 BTU/hr (27.84 kW) output heat. Common sizes: 40,000 BTU/hr (11.72 kW) for small homes/apartments; 60,000 BTU/hr (17.58 kW) for 1,200-1,800 sq ft; 80,000 BTU/hr (23.44 kW) for 1,800-2,400 sq ft; 100,000 BTU/hr (29.31 kW) for 2,400-3,000 sq ft; 120,000+ BTU/hr (35.17+ kW) for 3,000+ sq ft or cold climates. Heat Loss Calculation: Proper furnace sizing requires Manual J heat loss calculation considering insulation R-values, window quality, infiltration, climate zone. Rule of thumb (approximation only): 30-60 BTU/hr per sq ft depending on climate and insulation. Cold climate (Minnesota, Maine), poor insulation: 60 BTU/hr/sq ft; moderate climate (Virginia, Kansas), average insulation: 40-50 BTU/hr/sq ft; mild climate (Georgia, California), good insulation: 30-35 BTU/hr/sq ft. Example: 2,000 sq ft house in cold climate = 2,000 × 50 = 100,000 BTU/hr (29.31 kW) heat loss, requires 100,000+ BTU/hr furnace. Oversizing Consequences: Furnace 50%+ oversized causes short cycling (frequent on/off), uneven heating, reduced efficiency, higher fuel costs, shorter equipment life. Proper sizing: furnace capacity 15-25% above calculated heat loss. Boiler Systems: Hydronic (water) heating systems use boilers rated in BTU/hr or kW. Residential: 50,000-150,000 BTU/hr (14.66-43.97 kW); commercial: 200,000+ BTU/hr (58.62+ kW). Boiler sizing includes domestic hot water load if combo system. Example: 100,000 BTU/hr (29.31 kW) space heating + 40,000 BTU/hr (11.72 kW) water heating = 140,000 BTU/hr (41.03 kW) boiler required. Electric Resistance Heat: 100% efficient (all electrical energy becomes heat), but expensive to operate. Electric furnace/baseboard capacity equals electrical input. 10 kW electric heater produces 10 kW (34,121 BTU/hr) heat output. Common sizes: 5 kW (17,061 BTU/hr) per zone; 10-15 kW (34,121-51,182 BTU/hr) whole-home furnace. Converting BTU/hr to kW shows electrical demand: 80,000 BTU/hr resistance heat = 23.44 kW electrical load—requires 100+ amp service at 240V. Understanding kW-BTU/hr conversion enables proper heating equipment sizing, fuel vs electric cost comparisons (gas furnace BTU/hr vs electric heater kW), and electrical service planning for electric heating systems.

Building Thermal Load Calculations

HVAC design requires calculating building cooling and heating loads in BTU/hr or kW to properly size equipment. Manual J Residential Load Calculation: ACCA (Air Conditioning Contractors of America) Manual J is industry standard for residential thermal load calculation. Factors: wall/ceiling/floor insulation R-values, window U-factors and SHGC (solar heat gain coefficient), infiltration rate (ACH—air changes per hour), internal heat gains (occupants, appliances, lighting), climate data (design temperatures, humidity). Output: cooling load in BTU/hr and heating load in BTU/hr. Example result: 2,000 sq ft home—36,000 BTU/hr (10.55 kW) cooling load, 50,000 BTU/hr (14.66 kW) heating load. Room-by-Room Calculation: Proper design calculates each room's load separately for optimal duct sizing and comfort. Example: Master bedroom 350 sq ft—4,200 BTU/hr (1.23 kW) cooling; living room 450 sq ft—6,300 BTU/hr (1.85 kW) cooling; kitchen 250 sq ft—4,500 BTU/hr (1.32 kW) cooling including appliance heat gain. Sum of rooms = total load. Commercial Load Calculation: Larger buildings use more detailed methods (ASHRAE loads, energy modeling software). Includes occupancy diversity (not all spaces at peak simultaneously), ventilation requirements (ASHRAE Standard 62), process loads (data centers, kitchens, laboratories), solar orientation and shading. Commercial buildings: 200-400 sq ft per ton (600-1,200 sq ft per kW) cooling, highly variable by building type. Office: 300-400 sq ft/ton; restaurant: 100-150 sq ft/ton (high occupancy and kitchen loads); retail: 250-350 sq ft/ton. Cooling Load Components: Sensible heat (temperature change): walls/roof/windows conduction, infiltration, occupants, equipment, lighting. Latent heat (humidity): moisture from people, cooking, outdoor air infiltration. Total cooling load = sensible + latent. Example: Total 36,000 BTU/hr (10.55 kW)—28,000 BTU/hr (8.21 kW) sensible, 8,000 BTU/hr (2.34 kW) latent. Sensible/total ratio affects dehumidification—low ratio needs enhanced dehumidification equipment. Safety Factors: Add 10-20% to calculated loads for uncertainty and future additions. Example: Calculated 42,000 BTU/hr (12.31 kW) × 1.15 = 48,300 BTU/hr—specify 48,000 BTU/hr (4-ton) unit. Avoid excessive oversizing (25%+) causing short cycling and inefficiency. Converting between BTU/hr and kW allows engineers to use US load calculation methods (output in BTU/hr) with international equipment specifications (rated in kW), verify calculations against rules of thumb in either unit system, and communicate with contractors familiar with different measurement systems for seamless project execution.

Energy Efficiency Metrics

HVAC efficiency ratings use both BTU/hr and kW requiring conversions for accurate comparison. EER (Energy Efficiency Ratio): EER = BTU/hr cooling output ÷ watts electrical input. Measured at 95°F outdoor, 80°F indoor, 50% humidity. Example: 12,000 BTU/hr (3.52 kW) AC unit drawing 1,000 watts (1 kW) = EER 12. Higher EER = more efficient. Modern units: EER 8-14; top efficiency: 14+. Converting EER to kW ratio: Divide cooling kW by electrical kW. Example: 3.52 kW cooling ÷ 1 kW electrical = 3.52 ratio (equivalent to EER 12—multiply kW ratio by 3.412 to get EER). SEER (Seasonal Energy Efficiency Ratio): Seasonal average efficiency accounting for varying outdoor temperatures (not just single condition like EER). SEER = total BTU/hr cooling ÷ total watt-hours over cooling season. Minimum US standards: 14-15 SEER (varies by region); high efficiency: 20-25+ SEER. SEER always higher than EER (seasonal averaging includes efficient operation at moderate temperatures). COP (Coefficient of Performance): COP = thermal output (kW) ÷ electrical input (kW). Dimensionless ratio used internationally. Heat pumps: COP 2-4.5; chillers: COP 3-6. Example: Heat pump producing 10 kW (34,121 BTU/hr) heating using 3 kW electrical = COP 3.33. Relationship: COP ≈ EER ÷ 3.412. Example: EER 12 ≈ COP 3.52. HSPF (Heating Seasonal Performance Factor): Seasonal heating efficiency = total BTU/hr heating ÷ total watt-hours over heating season. Minimum: HSPF 8.2; high efficiency: 10-13+. Operating Cost Calculation: Annual cost = (cooling load BTU/hr × hours × electricity rate) ÷ (SEER × 1,000). Example: 36,000 BTU/hr load, 1,000 hours/year, $0.12/kWh, SEER 16. Cost = (36,000 × 1,000 × 0.12) ÷ (16 × 1,000) = $270/year. Converting to kW: 10.55 kW load, 1,000 hours, COP 3.52 (≈ SEER 12, using conservative estimate). Electrical consumption = 10.55 kW ÷ 3.52 = 3 kW input × 1,000 hours = 3,000 kWh × $0.12 = $360/year. Comparing Equipment Efficiency: International equipment rated COP vs US equipment rated SEER/EER. Convert for comparison: European chiller COP 4.5 = EER 15.4 (COP × 3.412). US heat pump HSPF 10 ≈ COP 2.93 average (HSPF ÷ 3.412). Understanding these conversions enables accurate efficiency comparison across different rating systems and informed equipment selection based on lifecycle operating costs.

Why Choose RevisionTown's kW to BTU/hr Converter?

RevisionTown's professional kilowatts to BTU per hour converter provides: (1) Exact Precision—Uses standardized conversion factor 3,412.14 (1 kW = 3,412.14 BTU/hr) for perfect accuracy matching international HVAC standards; (2) Bidirectional Conversion—Seamlessly convert kW↔BTU/hr with dedicated tabs for flexibility in HVAC design workflows; (3) Bulk Processing—Convert multiple equipment ratings simultaneously for comprehensive system comparison and multi-zone HVAC design; (4) Quick Reference—Instant access to common HVAC equipment ratings from window AC units to commercial chillers with corresponding ton ratings; (5) Formula Transparency—View exact mathematical conversions for educational purposes, verification, and client documentation; (6) HVAC Focus—Specifically designed for heating, cooling, and thermal power applications with relevant capacity ranges and equipment examples; (7) Mobile Optimized—Use on smartphones during job sites, equipment selection, contractor meetings, and building assessments; (8) Zero Cost—Completely free professional tool with no registration, advertisements, subscriptions, or usage limitations; (9) Professional Accuracy—Trusted by HVAC engineers, mechanical engineers, energy auditors, building designers, HVAC contractors, facility managers, architects, home inspectors, and students for critical thermal power conversions in HVAC system design, equipment specifications, thermal load calculations, energy efficiency analysis, building code compliance, electrical load planning, equipment procurement, international specification comparison, and all heating, ventilation, air conditioning, and refrigeration applications requiring exact translations between metric kilowatts and imperial BTU per hour for professional HVAC design work, accurate equipment sizing, energy auditing, and seamless integration of international equipment into US building projects worldwide.

❓ Frequently Asked Questions

How many BTU/hr is 1 kW?

1 kilowatt equals 3,412.14 BTU per hour. Formula: 1 kW = 3,412.14 BTU/hr (often rounded to 3,412 BTU/hr). This is the exact conversion between SI power units (kW) and imperial thermal power (BTU/hr). Example: A 1 kW electric space heater produces 3,412 BTU/hr of heat output. A 5 kW heater produces 17,061 BTU/hr.

How do you convert kW to BTU/hr?

To convert kilowatts to BTU per hour, multiply by 3,412.14. Formula: BTU/hr = kW × 3,412.14. Examples: 3.5 kW × 3,412.14 = 11,943 BTU/hr (1-ton AC); 5 kW × 3,412.14 = 17,061 BTU/hr; 10 kW × 3,412.14 = 34,121 BTU/hr (3-ton AC); 15 kW × 3,412.14 = 51,182 BTU/hr (4-ton system). This conversion is essential for HVAC equipment sizing and thermal capacity calculations.

How many BTU/hr is 3.5 kW?

3.5 kilowatts equals 11,943 BTU per hour. Calculation: 3.5 kW × 3,412.14 = 11,942.49 BTU/hr (typically rounded to 12,000 BTU/hr in HVAC specifications). This is a standard 1-ton window or wall air conditioner capacity suitable for cooling 400-550 square feet (small bedroom, office, or living room with normal insulation and moderate sun exposure).

How do you convert BTU/hr to kW?

To convert BTU per hour to kilowatts, divide by 3,412.14 or multiply by 0.000293071. Formula: kW = BTU/hr ÷ 3,412.14. Examples: 12,000 BTU/hr ÷ 3,412.14 = 3.52 kW (1-ton AC); 18,000 BTU/hr ÷ 3,412.14 = 5.28 kW (1.5-ton); 24,000 BTU/hr ÷ 3,412.14 = 7.03 kW (2-ton); 36,000 BTU/hr ÷ 3,412.14 = 10.55 kW (3-ton); 48,000 BTU/hr ÷ 3,412.14 = 14.07 kW (4-ton).

What is BTU/hr used for?

BTU/hr measures thermal power—the rate of heat energy transfer. Primary HVAC uses: Air conditioner cooling capacity (6,000-60,000+ BTU/hr for residential units); Furnace heating output (40,000-150,000 BTU/hr for homes); Heat pump capacity (heating and cooling ratings); Boiler capacity (50,000-200,000+ BTU/hr residential/commercial); Water heater recovery rate (how fast water is heated); Building heat loss/gain (thermal load calculations). BTU/hr is the standard US HVAC industry unit for equipment specifications and system design.

How many BTU/hr is a 1-ton air conditioner?

A 1-ton air conditioner equals 12,000 BTU/hr cooling capacity. The "ton" terminology refers to the cooling effect of melting one ton (2,000 pounds) of ice over 24 hours. In kilowatts: 1 ton = 12,000 BTU/hr = 3.52 kW cooling capacity. Common residential AC sizes: 1-ton (12,000 BTU/hr, 3.52 kW) for 400-600 sq ft; 1.5-ton (18,000 BTU/hr, 5.28 kW) for 600-900 sq ft; 2-ton (24,000 BTU/hr, 7.03 kW) for 1,000-1,400 sq ft; 3-ton (36,000 BTU/hr, 10.55 kW) for 1,500-2,100 sq ft; 4-ton (48,000 BTU/hr, 14.07 kW) for 2,000-2,800 sq ft; 5-ton (60,000 BTU/hr, 17.58 kW) for 2,500-3,500 sq ft.

How many kW is a 24,000 BTU air conditioner?

A 24,000 BTU/hr air conditioner has 7.03 kW cooling capacity. Calculation: 24,000 BTU/hr ÷ 3,412.14 = 7.03 kW. This is a 2-ton AC unit suitable for cooling 1,000-1,400 square feet (typical apartment, small house, or large master bedroom with adjoining spaces). Note: Cooling capacity (7.03 kW thermal) ≠ electrical power consumption. Actual electrical draw: typically 2-2.5 kW depending on efficiency (EER 8-12). High-efficiency units draw less electricity for same cooling output.

Why does the US use BTU/hr instead of kW?

The US uses BTU/hr for HVAC because: (1) Historical tradition—BTU established in imperial system before widespread metric adoption; (2) Industry standardization—Entire US HVAC industry (manufacturers, distributors, contractors, training programs, code requirements) built around BTU/hr over 100+ years; (3) Consumer familiarity—Homeowners understand "12,000 BTU air conditioner" from decades of marketing and usage; (4) Existing infrastructure—All sizing charts, load calculation software, reference materials, and equipment specifications use BTU/hr. However, commercial specifications increasingly include kW, and international manufacturers list both units. Global trend: Most countries use kW exclusively; US gradually adopting dual BTU/hr and kW labeling for international equipment compatibility.

Shares: